This site uses cookies to remember your language and measure which pages help. Accept all, or keep only what is necessary. Details in our Privacy policy.

Skip to main content

Q4 machinery sourcing week: container programmes up to 12% off

Claim offer

Earthworks & site

All use cases →
6 industry domains · 29 use-case pages · one equipment recommendation eachAll industry solutions →
CMSELL
Behind every order, one sourcing team

From factory search and audit to shipment and spares — the same people see it through, so you are not handed between desks.

About CMSELL

Before you pay, lock the risk down

Escrow release · pre-shipment inspection · dispute handling · after-sales spares
100%Orders under escrow
48hTerms & quote reply
4Protection points
How protection worksPayment methodsProtection terms go straight into the order — no separate contract to sign. Read the full terms
  1. Home
  2. Industry
  3. Energy & Utilities
  4. Standby Power Sizing: kW, kVA and Motor Starts
CMSELL · INDUSTRY

Standby Power Sizing: kW, kVA and Motor Starts

Steady load, starting kVA and step loading set generator size, not the nameplate kW. A four-step sizing path for 50–500 kW standby sets and their derates.

High-voltage electrical substation in an open field
Utility supply fails at the worst moment; the set has to carry the load step, not just the steady load.

Size a standby set on three numbers: running kW, the largest motor start in kVA, and the load step the set must accept. Nameplate kW alone will leave you with a set that stalls on the first pump start or runs at 30% load and glazes its cylinders.

1Why it matters

A standby generator is judged on the worst ten seconds of its life, not on a typical afternoon. Undersizing shows up as voltage dip, breaker trips, or a set that never reaches rated frequency before the next load arrives. Oversizing is quieter but expensive: lightly loaded diesel sets wet-stack, consume more fuel per kWh and need earlier overhaul.

2The four-step sizing path

Step Measure Rule of thumb
1 Steady running load (kW) Sum measured or nameplate loads, then apply a diversity factor of 0.7–0.9
2 Largest motor starting kVA Direct-on-line start draws 5–7 × rated kVA; soft start 2.5–3.5 ×
3 Load step acceptance Set should accept the largest step at ≤ 15% transient dip and recover within a few seconds
4 Altitude, temperature, enclosure Derate for site conditions; a silent canopy costs airflow and adds a derate

A 200 kW class set such as the CM200S is a typical answer for a small plant with a 120–150 kW steady load and a 55–75 kW motor start, provided the start is soft-started or star-delta. Direct-on-line starting of the same motor can push the requirement a class higher.

3Where projects go wrong

  1. Adding nameplate kW and stopping. Diversity and power factor are ignored, so the set is sized 20–30% too large.
  2. Ignoring starting kVA. Motors, not resistive loads, decide the transient. One 75 kW DOL motor can dominate the sizing.
  3. Forgetting the enclosure derate. A silent canopy in 45 °C ambient can cost 10–15% of rated output.
  4. No load banking. A set that only ever runs at 25% load will not prove it can carry the site when the utility fails.

4Numbers to fix before you enquire

Item Range Effect on sizing
Steady load 30–400 kW Base size
Largest motor 7.5–110 kW, start method Sets transient requirement
Power factor 0.8–0.9 Converts kW to kVA
Ambient / altitude 35–50 °C, 0–2000 m Derate factor
Autonomy required 4–8 h Fuel tank size, not set size

5Tools & next

Send the load list with motor start methods and the site ambient; we will return a set size with the derate stated separately. Related reading: how to read an engine emission standard correctly, and how pump head calculations interact with generator starting loads.

Key facts. Standby generator sizing uses three numbers: steady running kW, the largest motor starting kVA, and the load step the set must accept. Direct-on-line motor starting draws roughly 5–7 times rated kVA, soft starting about 2.5–3.5 times, which is why the starting method can move the required set size by a whole class. Power factor of 0.8–0.9 converts kW to kVA and is often omitted when buyers add nameplate figures. Silent enclosures and high ambient reduce available output by roughly 10–15%. A 200 kW set typically serves a 120–150 kW steady load with a soft-started 55–75 kW motor. This article covers standby set sizing only; it does not cover paralleling, switchgear protection settings or utility interconnection approvals.

Safety: generator connection, earthing and changeover must be designed and installed by qualified electrical personnel under local regulations. Sizing figures are for planning only.

Published 25 November 2026 · 4 min read · Industry column.

Need this checked against your site?

Send the working condition, the quantity and the destination port. The desk answers with a written specification and a traceable price — not a brochure.

Sourcing for this application

Tell us the machine, quantity and destination. We match audited factories, return comparable quotations, and handle inspection and freight if you need them.

Factories that build equipment for this application:
WhatsApp